15KA MCB AC 415V 63A High Breaking Capacity

Securing critical industrial AC networks against devastating overcurrents, this 15ka mcb delivers exceptionally high ultimate short-circuit isolation. The ETM1-63UH series functions as a heavy-duty industrial mcb 15ka, specifically engineered to manage rated currents up to 63A and aggressively clear severe electrical faults across demanding commercial distribution boards.

Request a Quote

Pricing is quoted per order — tell us your quantity and destination and our sales team will respond with a full offer.

ModelETM1-63UH
AvailabilityIn stock
  • CE & TUV certified
  • Worldwide shipping
  • OEM & ODM support

Product Features of the 15KA MCB

Engineered with premium halogen-free thermoplastics, this 15ka mcb guarantees long-term structural resilience while allowing comprehensive modular accessory integration.

  • Extreme Short-Circuit Isolation: Achieves an ultimate short circuit breaking capacity (Icu) of 15kA, effortlessly protecting systems against massive high-inrush faults.
  • Touch-Safe Architecture: Features IP20 finger-protected incoming and outgoing terminals, strictly preventing hazardous operator contact during active panel maintenance.
  • Maximum Wiring Versatility: Supports flexible/rigid cables (up to 25mm²), standard pin-type busbars, and heavy-duty fork-type busbars for simultaneous dual connections.
  • Instant Operational Feedback: Integrates a prominent red/green mechanical contact position indicating device for immediate switching status verification.
  • Eco-Conscious Durability: Built using state-of-the-art recyclable housing materials, fully conforming to strict international RoHS environmental standards.

ETM1-63UH Structural Design & Product Tips

The ergonomic outer shell incorporates specific structural enhancements to streamline complex B2B installations and lifecycle management.

ETM1-63UH Product Tips

  1. Reversible Connection: Supports bidirectional line and load terminal routing for highly adaptable industrial panel configurations.
  2. EAN-13 Barcodes: Pad-printed directly on the side enclosure for rapid B2B inventory scanning and precise warehousing tracking.
  3. Handle Lock Position: Specifically molded slot designed to secure the toggle with a mechanical padlock during vital line maintenance.
  4. Amperage Visibility: High-contrast front printing explicitly displaying the rated current up to 63A.
  5. PIN / Fork Busbar Ready: Specially designed terminal cavities to accept simultaneous fork busbar and standard cable connections.
  6. Indication Window: Instant visual confirmation of the contact open/close position (green OFF / red ON).

Commercial Applications for the 15KA MCB

Deploying the ETM1-63UH secures the most demanding distribution nodes, establishing a highly dependable iec 60947 mcb framework for any robust industrial setup.

Applications & Use Cases

  • Industrial Equipment Protection: Secures robust AC power supply lines feeding heavy industrial machinery requiring a dependable 15ka industrial circuit breaker.
  • Commercial Building Networks: Isolates extensive commercial lighting and HVAC circuits efficiently, utilizing the mcb 15ka industrial for standard office complexes.
  • Public Facility Assurance: Functions as the core protective 15ka miniature circuit breaker in public infrastructure, safeguarding vital electrical panels from catastrophic overload damage.

Technical Specifications with the 15KA MCB

Evaluate the comprehensive thermal-magnetic tolerances below to seamlessly integrate this high breaking capacity 15ka mcb into your AC electrical distribution panels.

General, Electrical & Mechanical Data

General & Technical Data (IEC/EN 60947-2)
Electrical Parameters
ProtectionOvercurrent and short circuitType of tripThermal-magnetic
No. of poles1P, 2P, 3P, 4PRated frequency50/60Hz
Rated operational voltage (Ue)1P: 110/230V, 120/240V, 230/400V, 240/415V AC
2P, 3P, 4P: 230/400V, 240/415V, 400/415V AC
Rated current (In)1, 2, 3, 4, 5, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63A
Rated insulation voltage (Ui)440VRated impulse withstand (Uimp)6kV (1.2/50μs)
Ultimate short-circuit capacity (Icu)15kAService short-circuit capacity (Ics)7.5kA
Mechanical & Installation Data
Electrical / Mechanical life10,000 Cycles / 20,000 CyclesProtection degreeIP20
Terminal connection typeCable / Pin-type / Fork-type busbarMax. terminal size16mm² flexible / 25mm² rigid
Operating ambient temp.-25°C ~ +55°CFire resistance (glow-wire)960±15°C (Enclosure)
Auxiliary Expansion SupportAuxiliary Contact, Alarm Contact, Shunt Release, Voltage Loss Release, Under/Over-voltage Release, Mechanical Interlock (All Supported)

Tripping Characteristics

The thermal and magnetic release parameters strictly dictate the precise trip times under varying load states.

Tripping Characteristic Curve 15ka mcb

Data acc. to IEC/EN 60947-2 (Rated current ≤ 63A)
Tripping CharacteristicInitial StateTest Current (A)Trip Time (t)Result ExpectedAmbient Temp.
Thermal releaseCold state1.05In≥ 1hNo trip30±2°C
Hot state (Follows above test)1.30In< 1hTrip
Magnetic releaseCold state8In≤ 0.2sNo tripNormal temperature
12In< 0.2sTrip

Temperature Derating Table

Use the specific correction factors below to adjust the rated current based on the ambient installation temperatures.

Rated Current (A)Correction Factor for Ambient Temperature
-40°C-30°C-20°C-10°C0°C10°C20°C30°C40°C50°C60°C70°C
11.331.291.251.21.151.111.0510.940.880.820.75
22.672.582.492.42.312.212.1121.891.761.631.49
34.03.93.73.63.53.33.232.82.62.42.2
45.35.25.04.84.64.44.243.83.53.33.0
56.76.56.316.15.85.55.2554.74.34.03.7
68.07.77.57.26.96.66.365.75.34.94.5
1013.312.912.512.011.511.110.5109.48.88.27.5
1621.320.720.019.218.517.716.91615.114.113.111.9
2026.725.824.924.023.122.121.12018.917.616.314.9
2533.332.331.230.028.927.626.42523.622.020.418.6
3242.741.339.938.537.035.433.73230.228.226.123.9
4053.351.649.948.146.244.242.24037.735.332.729.8
5066.764.562.460.157.755.352.75047.144.140.837.3
6384.081.378.675.772.769.666.46359.455.651.447.0

Dimensions and Wiring of the 15KA MCB

Verify the exact modular DIN rail footprints and dual terminal spacing below to guarantee perfect panel fitment for this high breaking capacity 15ka mcb.

Wiring Diagram

15ka mcb Wiring Diagram

Dimension (mm)

15ka mcb Dimension

Physical & Mounting Specifications

Poles ConfigurationWidth (mm)Height (mm)Total Depth (mm)
1P18 mm81 mm76 mm
2P36 mm81 mm76 mm
3P54 mm81 mm76 mm
4P72 mm81 mm76 mm