| General Data |
| Protection |
Overcurrent and short circuit |
| Type of trip |
Thermal-magnetic |
| No. of poles |
1P, 2P, 3P, 4P |
| Rated operational voltage (Ue) |
1P: 110/230V, 120/240V, 230/240V, 240/415V AC
2P, 3P, 4P: 230/400V, 240/415V, 400/415V AC |
| Rated current (In) |
1, 2, 3, 4, 5, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63A |
| Rated frequency |
50/60Hz |
| Rated insulation voltage (Ui) |
440V |
| Rated impulse withstand voltage (Uimp) |
6kV (1.2/50µs) |
| Dielectric test voltage |
2kV (50/60Hz, 1 min.) |
| Fire resistance (glow-wire test) |
960±15°C (Enclosure); 650±10°C (Handle) |
| Pollution degree |
2 |
| Data acc. to IEC/EN 60898-1 |
| Rated short-circuit capacity (Icn) |
6kA |
| Rated service short-circuit breaking capacity (Ics) |
6kA |
| Energy limiting class |
3 |
| Thermal tripping characteristics |
1.13xIn No tripping within an hour; 1.45xIn Tripping within an hour |
| Instantaneous tripping characteristics |
B: 3In-5In; C: 5In-10In; D: 10In-20In |
| Data acc. to IEC/EN 60947-2 |
| Rated ultimate short circuit breaking capacity Icu |
6kA |
| Rated service short circuit breaking capacity Ics |
6kA |
| Thermal tripping characteristics |
1.05xIn No tripping within an hour; 1.3xIn Tripping within an hour |
| Instantaneous tripping characteristics |
8In-12In |
| Mechanical Data & Installation |
| Electrical life / Mechanical life |
10,000 Cycles / 20,000 Cycles |
| Contact position indication |
Green OFF / Red ON |
| Protection degree |
IP20 |
| Reference temperature |
30°C |
| Operating ambient temperature |
-25°C ~ +55°C (with daily ≤35°C) |
| Storage temperature |
-30°C ~ +70°C |
| Terminal connection type |
Cable / Pin-type / Fork-type busbar |
| Terminal block / Max. tightening torque |
Screw press-connected / 2.5 N.m |
| Max. terminal size for cable |
16mm² flexible / 25mm² rigid |
| Mounting type / Incoming method |
Mounting on 35mm DIN rail / Bi-Directional |
| Auxiliary for remote tripping or signaling |
| Available Accessories |
Auxiliary Contact, Alarm Contact, Shunt Release, Voltage Loss Release, Over-voltage Release, Undervoltage Release, Mechanical Interlock |