Cylinder Fuse DC 1500V 35A 50kA PV Array Protection

Intercepting massive overload transients in 1500V DC photovoltaic networks, this robust Cylinder Fuse secures utility-scale commercial installations. The EKFL15D10L series manages up to 35A loads and an exceptional 50kA breaking capacity to maintain continuous high-voltage distribution.

Request a Quote

Pricing is quoted per order — tell us your quantity and destination and our sales team will respond with a full offer.

ModelEKFL15D10L
AvailabilityIn stock
  • CE & TUV certified
  • Worldwide shipping
  • OEM & ODM support

Product Features of the Cylinder Fuse

Engineered specifically for demanding solar environments, this Cylinder Fuse guarantees uncompromised electrical isolation across heavy-duty DC switchgear.

  • High Voltage Capacity: Operates safely at 1500V DC across an 8A to 35A current range, ensuring reliable performance in modern PV plants.
  • Robust Fault Withstand: Resists massive grid anomalies utilizing a 50kA rated breaking capacity and a fast-acting gPV utilization category.
  • Thermal Efficiency: Features a high-grade quartz sand filling material, effectively minimizing arc energy and maintaining a low rated power dissipation (≤9.3W at 1In).
  • Standardized Form Factor: Housed in a compact 10x85mm fuse cylinder to optimize panel space within commercial combiner boxes and inverter inputs.

Industrial Applications for the Cylinder Fuse

Deploying the EKFL15D10L minimizes catastrophic electrical hazards across high-voltage infrastructures relying on a dependable Cylinder Fuse.

Applications & Use Cases

  • Solar Photovoltaic Arrays: Secures independent utility-scale strings and arrays against destructive direct current short circuits.
  • DC Combiner Boxes: Functions as a primary protective node before aggregated power reaches the central PV inverter.
  • Charge Controllers: Shields high-voltage energy storage routing systems and solar charge controllers from massive overload transients.

Technical Specifications with the Cylinder Fuse

Evaluate the precise direct current parameters below to align this Cylinder Fuse perfectly with your IEC60269-6 distribution requirements.

Main Technical Data

Electrical Parameters
StandardIEC60269-6
Utilization categorygPV
Rated voltage1500 VDC
Rated current8A ~ 35A
Rated breaking capacity50kA
Arc voltage limits3500V
Rated power dissipation (at 0.7In)≤ 5.0W
Rated power dissipation (at 1.0In)≤ 9.3W
Mechanical & Environmental Data
Size10mm x 85mm
Filling materialQuartz Sand
Operating temperature-40°C to +80°C
Storage temperature-40°C to +90°C
CertificatesCE, CB, TUV

I²t Values and Power Loss

ModelRated Current (A)I²t (Amps² seconds)Power Loss (W)
Pre-arcingTotal clear0.8In1.0In
EKFL15D10L022241.02.0
EKFL15D10L0336111.12.1
EKFL15D10L04414221.22.2
EKFL15D10L05511151.42.4
EKFL15D10L06630351.52.6
EKFL15D10L0889101.83.0
EKFL15D10L1010981202.23.5
EKFL15D10L121212142.53.8
EKFL15D10L15151704003.04.8
EKFL15D10L202034653.56.2
EKFL15D10L25254.05505.07.2
EKFL15D10L30304.57506.38.3
EKFL15D10L32321167926.88.9
EKFL15D10L35351439807.09.3

Dimensions and Wiring of the Cylinder Fuse

Verify exact 10x85mm enclosure and fuse clip compatibility using the physical footprints associated with this Cylinder Fuse.

cylinder fuse

Dimensional Data (mm)

ModelDiameterTotal LengthCap Length
EKFL15D10L10.3 ± 0.1 mm85.0 ± 1.2 mm10.5 mm (max)