| Input DC (PV side) |
| Recommended max. PV array size | 250kW |
| Max. usable PV input power | 250kW |
| Max. input voltage | 1000V |
| Rated voltage | 600V |
| Start-up voltage | 180V |
| MPPT voltage range | 150-950V |
| Max. input current | 10 x 42A |
| Max. short circuit current | 10 x 60A |
| MPPT number / max. input strings | 10 / 20 |
| Battery |
| Battery type | Li-ion |
| Battery voltage range | 300-950V |
| Max. charge/discharge current | 200A / 100A+100A |
| Number of battery ports | 2 |
| Max. charge/discharge current per port | 100A |
| Communication | CAN / RS485 |
| Max. battery energy | 256kWh |
| Output AC (Grid side) |
| Rated output power | 125kW |
| Max. apparent output power | 125kVA |
| Rated grid voltage | 3/N/PE, 220/380V, 230/400V |
| Rated grid frequency | 50/60Hz |
| Rated grid output current | 189.9A / 180.4A |
| Power factor | >0.99 (0.8 leading – 0.8 lagging) |
| THDi | 3% |
| Input AC (Grid side) |
| Max. input current | 250A |
| Output AC (Back-up) |
| Rated output power | 125kW |
| Max. apparent output power | 1.2x rated, 100s; 1.4x rated, 10s; 1.6x rated, 200ms |
| Back-up switch time | <10ms |
| Rated output voltage | 3/N/PE, 220/380V, 230/400V |
| Rated frequency | 50/60Hz |
| THDv (@linear load) | <2% |
| Input AC (Generator) |
| Rated output power | 125kW |
| Max. apparent output power | 125kVA |
| Rated grid voltage | 3/N/PE, 220/380V, 230/400V |
| Rated grid frequency | 50/60Hz |
| Efficiency |
| Max. efficiency | 97.6% |
| EU efficiency | 97.2% |
| BAT charged/discharged to AC max. efficiency | 97.0% |
| Protection |
| Anti-islanding protection | Yes |
| Output overcurrent protection | Yes |
| Short circuit protection | Yes |
| Integrated DC switch | Yes |
| DC reverse-polarity protection | Yes |
| Surge protection | DC Type II / AC Type II |
| Integrated AFCI 2.0 | Optional (Brazil: yes) |
| Protection class / overvoltage category | I / II |
| General Data |
| Max. allowable phase imbalance (grid & back-up) | 100% |
| Max. power per phase (grid & back-up) | 41.66kW |
| Topology | Transformerless |
| Operating ambient temperature | -25 to +60°C |
| Relative humidity | 0-100% |
| Ingress protection | IP66 |
| Cooling concept | Intelligent fan-cooling |
| Max. operating altitude | 3000m |
| Features |
| PV connection | MC4 quick connection plug |
| Battery connection | Terminal connector |
| AC connection | Terminal block |
| Display | 7.0″ LCD display & Bluetooth + APP |
| Communication | CAN, RS485-115200, Ethernet; optional Wi-Fi, Cellular, LAN |
| Standards |
| Grid connection standard | G99, VDE-AR-N4105/VDE-V0124, EN50549-1&2/EN50549-10, VDE0126/UTE C15/VFR:2019, NTS631/RD1699/RD244/UNE206006/UNE206007-1, CEI0-21, C10/11, NRS097-2-1, TOR, EIFS2018.2, IEC62116, IEC61727, IEC60068, IEC61683, EN50530, MEA, PEA, PORTARIA No.140 |
| Safety / EMC standard | IEC/EN62109-1/-2, IEC/EN61000-6-2/-4, EN55011 |