40kA Surge Arrester – Type 2 AC Surge Protective Device

The ETU5-T2-40 is a 40kA surge arrester for low-voltage AC power distribution. It delivers Type 2 / Class II protection with In 20kA and Imax 40kA (8/20μs) against lightning-induced surges and switching overvoltages in building and industrial installations.

Request a Quote

Pricing is quoted per order — tell us your quantity and destination and our sales team will respond with a full offer.

ModelETU5-T2-40
AvailabilityIn stock
  • CE & TUV certified
  • Worldwide shipping
  • OEM & ODM support

Product Features of 40kA Surge Arrester

This 40kA surge arrester combines high discharge capacity with installation and maintenance features designed for panel builders and electrical contractors. It offers dependable surge protection 40kA (Imax, 8/20μs) per protection mode, and is built as a type 2 surge arrester 40kA unit for distribution boards.

  • Type 2 / Class II protection: In 20kA and Imax 40kA (8/20μs) for both L-N and N-PE modes.
  • Multi-system support: suitable for TN-S, TN-C and TT systems.
  • Keyed N-PE module: helps prevent incorrect replacement while improving installation safety and maintenance convenience.
  • Pluggable cartridge: modules can be replaced without changing the base.
  • Visual status indication: green = OK, red = defect (L-N); yellow indicates the N-PE module.
  • Optional remote signaling: “S” versions provide a changeover contact (11-12-14) for SPD disconnect information.
  • Protective elements: high energy MOV, with MOV and GDT in 1P+NPE and 3P+NPE versions.
  • Fast response: ≤25ns (L-N) and ≤100ns (N-PE).
  • Uniform panel layout: appearance and mounting dimensions match the T Series, allowing side-by-side installation.
  • Standard and safety: IEC/EN 61643-11, CE marked, UL94-V0 enclosure, IP20 (built-in).

Commercial Applications of 40kA Surge Arrester

A 40kA surge arrester suits commercial and industrial power systems where equipment downtime and surge damage carry a high cost. As a 40kA surge protection device, the ETU5-T2-40 is installed at the distribution level to limit overvoltages before they reach sensitive loads.

Applications & Use Cases:

  • Building Main Distribution: protection at main switchboards and incoming supply points.
  • Branch Distribution Panels: second-stage protection in sub-distribution boards.
  • Industrial Control Systems: protects control cabinets, drives, and automation equipment.
  • Telecom & Data Rooms: protects servers, racks, and communication infrastructure.

Technical Specifications of 40kA Surge Arrester

The table below lists the electrical and mechanical data of the 40kA surge arrester. Specified as a class 2 surge arrester under IEC/EN 61643-11, it is available in five Uc ratings: 150V, 275V, 320V, 385V and 440V.

Configuration by number of poles

Poles 1P 2P 3P 4P 1P+NPE / 3P+NPE
Network systems TN-S, TN-C, TT (only L-N) TN-S TN-C TN-S TT, TN-S
Mode of protection L-PE, N-PE (only TN-S), L-N L-PE, N-PE L-PEN L-PE, N-PE L-N, N-PE
Protective elements High Energy MOV High Energy MOV High Energy MOV High Energy MOV High Energy MOV and GDT

Voltage-dependent data

Max. continuous operating voltage (L-N) Uc 150V 275V 320V 385V 440V
Voltage protection level (L-N)/(N-PE) Up 0.8kV/1.5kV 1.3kV/1.5kV 1.5kV/1.5kV 1.8kV/1.5kV 2.0kV/1.5kV
Voltage protection level at 5kA Up 0.6kV 1.0kV 1.2kV 1.4kV 1.6kV

General data

Parameter Value
Max. continuous operating voltage (N-PE) Uc 255V
Nominal discharge current (8/20μs) (L-N)/(N-PE) In 20kA
Maximum discharge current (8/20μs) (L-N)/(N-PE) Imax 40kA
Response time (L-N)/(N-PE) tA ≤25ns / ≤100ns
Operating temperature range Tu -40°C to +80°C
Max. back-up fuse 125A gL/gG
Operating state/fault indication Green/Red (L-N), Yellow (N-PE)
Cross-section area (min./max.) 4mm² / 35mm²
Mounting 35mm DIN rail, EN 60715
Enclosure material Thermal plastic UL94-V0
Degree of protection IP20 (built-in)
Remote contacts (RC) Optional
RC switching capacity AC: 250V/0.5A; DC: 250V/0.1A; 125V/0.2A; 75V/0.5A
RC conductor cross section (max.) 16 AWG (solid) / 1.5mm² (solid)
Standard IEC/EN 61643-11

Model selection (ETU5-T2-40-[poles][Uc][S])

  • Ordering code: E = ETEK
  • T = T series; U5 = SPD series No.5
  • T2 = Class II / Type 2
  • 40 = Imax 40kA
  • poles = 1P, 2P, 3P, 4P, 1PN (1P+NPE), 3PN (3P+NPE)
  • Uc = 150, 275, 320, 385 or 440
  • S = with remote signaling
Poles 150V 275V 320V 385V 440V
1P ETU5-T2-40-1P150 ETU5-T2-40-1P275 ETU5-T2-40-1P320 ETU5-T2-40-1P385 ETU5-T2-40-1P440
2P ETU5-T2-40-2P150 ETU5-T2-40-2P275 ETU5-T2-40-2P320 ETU5-T2-40-2P385 ETU5-T2-40-2P440
3P ETU5-T2-40-3P150 ETU5-T2-40-3P275 ETU5-T2-40-3P320 ETU5-T2-40-3P385 ETU5-T2-40-3P440
4P ETU5-T2-40-4P150 ETU5-T2-40-4P275 ETU5-T2-40-4P320 ETU5-T2-40-4P385 ETU5-T2-40-4P440
1P+NPE ETU5-T2-40-1PN150 ETU5-T2-40-1PN275 ETU5-T2-40-1PN320 ETU5-T2-40-1PN385 ETU5-T2-40-1PN440
3P+NPE ETU5-T2-40-3PN150 ETU5-T2-40-3PN275 ETU5-T2-40-3PN320 ETU5-T2-40-3PN385 ETU5-T2-40-3PN440

Add the suffix “S” for the remote signaling version, for example ETU5-T2-40-1PN275S.

Dimensions and Wiring of 40kA Surge Arrester

The 40kA surge arrester is built on a 35mm DIN rail. Width is 18mm per module, so 1P to 4P versions measure 18mm, 36mm, 54mm and 72mm. A pluggable surge arrester class 2 cartridge can be replaced quickly when the status indicator turns red.

Dimension (mm)

 

40ka surge arrester

Basic circuit diagram

 

40ka surge arrester

Connection diagram

40ka surge arrester

Maintenance

 

40ka surge arrester

Remote signal terminal

 

40ka surge arrester

 

SPD OK SPD disconnect / defect
11-12 Closed 11-12 Open
11-14 Open 11-14 Closed

 