AC MCCB Breaker 1140V 100kA High Voltage Protection

Securing robust high-voltage AC distribution networks, the AC MCCB Breaker delivers reliable electro-magnetic fault isolation. The EKM7_AC_MCCB molded circuit breaker manages continuous loads up to 630A, guaranteeing 100kA short-circuit stability for industrial infrastructures.

Request a Quote

Pricing is quoted per order — tell us your quantity and destination and our sales team will respond with a full offer.

ModelEKM7_AC_MCCB
AvailabilityIn stock
  • CE & TUV certified
  • Worldwide shipping
  • OEM & ODM support

Product Features of the AC MCCB Breaker

Engineered to instantaneously interrupt severe alternating current faults, this AC MCCB Breaker ensures rigorous equipment safety through advanced arc elimination technologies.

  • Arc Suppression Technology: Features a short 50mm arcing distance with a standard arc suppression cover and three-layer free metal partition to prevent secondary system failures.
  • High Insulation Endurance: Delivers exceptional insulation performance with a rated impulse withstand voltage (Uimp) of 12kV and an insulation voltage of 1200V.
  • Core Patented Mechanics: Utilizes repulsion opening anti-drop technology and a new single breakpoint structure, providing more reliability than traditional double breakpoint designs.
  • Extreme Environment Resistance: Demonstrates robust anti-humidity, heat, salt spray, and mold resistance, supporting reverse inlet lines without capacity reduction.

Industrial Applications for the AC MCCB Breaker

Integrating the EKM7_AC_MCCB model minimizes critical downtime across specialized commercial and heavy-duty AC infrastructures.

  • Power Distribution Networks: Protects robust AC circuits operating between 690V and 1140V against overloads, short circuits, overvoltage, and undervoltage anomalies.
  • Heavy Machinery Operation: Functions as a highly dependable mccb ac device for the infrequent switching of industrial circuits and occasional heavy motor starting.
  • High-Altitude Substations: Maintains uncompromised power line stability in elevated installations, supporting altitudes up to 5000m with calculated derating.

Technical Specifications of the AC MCCB Breaker

Evaluate the comprehensive electro-magnetic parameters below to ensure this AC MCCB Breaker aligns precisely with your specific AC switchgear load calculations.

Certifications & Operating Conditions:

The EKM7_AC_MCCB strictly complies with the IEC60947-2 standard. It operates reliably in ambient temperatures ranging from -40°C to +70°C, requiring no thermal derating at +50°C.

Model Fast Selection Guide:

EKM7 Series MCCB Configuration
Product codeFrame sizeBreaking capacity levelPolesProduct AccessoriesColor code
EKM7320, 630M: ordinary type
H: high breaking type
3PSee accessory tableNone: off-white cover, black handle
D: dark gray cover, red handle

Technical Parameters:

ModelEKM7-320EKM7-630
Rated Frame Current Inm (A)320630
Rated current In (A)16, 20, 25, 32, 40, 50, 63, 75, 80, 100, 125, 140, 160, 180, 200, 225, 250, 320A225, 250, 320, 350, 400, 500, 630A
Pole3P
Rated working voltage Ue (V)380/415V, 690V, 800V, 1000V, 1140V
Rated insulation voltage Ui (V)1200V
Rated impulse withstand voltage Uimp (kV)12kV
Power frequency withstand voltage (1min) (V)3500V
Rated ultimate short-circuit breaking capacity Icu (kA)
M LevelAC380/415V, AC690V, AC800V, AC1000V50, 20, 20, 1260, 20, 20, 12
AC1140V1212
H LevelAC380/415V, AC690V, AC800V, AC1000V100, 50, 30, 20100, 65, 50, 32
AC1140V2020
Rated operating short-circuit breaking capacity Ics (kA)
M LevelAll Voltages50, 20, 20, 12, /60, 20, 20, 12, 12
H LevelAll Voltages100, 50, 30, 20, 12100, 65, 50, 32, 20
Mechanical life (cycles)15000
Electrical life (cycles)5000, 3000, 3000, 1000, 10005000, 3000, 3000, 1000, 1000
Arc distance (mm)50
Dimension W x L x H (mm)120 x 200 x 103158 x 325 x 177
Instantaneous release5In or 10In

Temperature & Altitude Derating Characteristics:

Applicable Working Environment and Compensation Coefficient
Ambient temperature10°C20°C25°C30°C40°C50°C60°C70°C
Compensation coefficient1.171.141.121.0610.960.870.76
Derating Coefficient Based On Altitude
Altitude (m)2000250030003500400045005000
Rated current1In0.99In0.98In0.97In0.96In0.95In0.94In
Rated voltage1Ue0.95Ue0.88Ue0.85Ue0.82Ue0.8Ue0.75Ue
Rated power frequency withstand voltage1U0.95U0.88U0.85U0.82U0.8U0.75U

Accessory Configuration Table:

AC MCCB Breaker

Dimensions and Wiring with the AC MCCB Breaker

Verify exact enclosure compatibility for this ac mccb device by referencing the structural footprints, required clearance spaces, and mounting hole configurations illustrated below.

Overall Dimensions (mm)

AC MCCB Breaker

ModelWW1W2LL1L2L3L4HH1H2H3ABd
EKM7-3201203811020026417827265710813710031.538161Ø5.5
EKM7-630158501482603252312296251421771345050215Ø6.5

Mounting Distance to Metal Parts (mm)

AC MCCB Breaker

ModelABCDF
EKM7-3205050505025
EKM7-6305050505020

Tripping Characteristics & Temperature Curves

Tripping Curve AC MCCB Breaker


Tripping Curve AC MCCB Breaker

Request a Quote

Get pricing for EKM7_AC_MCCB

Complete the form and our sales engineers will reply with pricing, lead time and certification documents.

Chat on WhatsApp